← All blogs

REGULATORY GUIDANCE

Does your chemical or solvent require PESO storage?

A solvent cannot be classified by flammability alone. Review its composition, the flash point of the finished product, and how it will be stored.

The three-check method

01 · COMPOSITIONWhat does it contain?

Check the current manufacturer SDS. Is it a liquid hydrocarbon, a hydrocarbon mixture, or an inflammable mixture containing a liquid hydrocarbon?

02 · FLASH POINTWhich petroleum class?

If it meets the petroleum definition, check the flash point of the finished commercial product for Class A, B or C.

03 · STORAGEWhat is proposed?

Review quantity, packaging, compatibility, handling activity and the facility’s actual approvals before confirming acceptance.

If it does not meet the petroleum definition: check the Inflammable Substances Act, 1952 and applicable notifications before deciding its regulatory route. The class table below applies to petroleum; products at 93°C or above have a separate statutory exemption.

Check 1 — What does the product contain?

The Petroleum Act, 1934 includes liquid hydrocarbons, mixtures of hydrocarbons and inflammable mixtures containing a liquid hydrocarbon in its definition of petroleum. Familiar examples include toluene, xylene, hexane, heptane, mineral spirits, solvent naphtha and petroleum distillates. Their exact commercial grades still need to be checked.

What about paints, thinners and adhesives?

A paint, thinner, printing ink, adhesive, cleaning solvent or resin solution can contain hydrocarbon solvents alongside resins, pigments, alcohols and additives. If the finished mixture is inflammable and contains a liquid hydrocarbon, it may meet the petroleum definition. The product name or main ingredient alone cannot settle this; obtain the manufacturer’s SDS and, where needed, a composition declaration.

Check 2 — What is the flash point?

Once the product has been established as petroleum, its finished-product flash point determines the statutory petroleum class. Do not use the flash point of just one ingredient.

Petroleum classes under Section 2 of the Petroleum Act
ClassFinished-product flash point
Class ABelow 23°C
Class B23°C or above, but below 65°C
Class C65°C or above, but below 93°C
93°C or aboveExempt from Chapter I under Section 11; other requirements may still apply

In short: composition and the statutory definition determine whether the product may be petroleum. Flash point determines its class after that. A low flash point alone does not make every chemical a petroleum product.

What if the liquid is not a hydrocarbon?

Do not automatically label it “Non-PESO.” The Inflammable Substances Act, 1952 identifies acetone, ethyl alcohol, methyl alcohol and wood naphtha as dangerously inflammable substances. The Petroleum Act provisions applied to a substance depend on applicable government notifications. Check the exact product and notifications before routing acetone, ethanol or methanol to a facility.

Check 3 — How will it be stored?

Product classification and a warehouse’s permission to accept it are separate decisions. Review maximum quantity, MS or HDPE drum, IBC or tank capacity, packaged or bulk storage, chemical compatibility, and any filling, decanting, repacking or transfer activity. Compare the proposal with the applicable licence, layout and conditions.

When is a PESO storage licence required?

After identifying a product as petroleum and confirming its class, review the quantity and storage method. Section 7 of the Petroleum Act provides limited exemptions under specified conditions; the figures below are not blanket permission to store a product.

Selected exemption limits under Section 7
Petroleum classLimited exemption
Class AUp to 30 litres, when it is not intended for sale and is kept in the receptacles specified by the Rules.
Class BUp to 2,500 litres in non-bulk storage, or 1,000 litres in bulk storage, subject to the statutory conditions.
Class CUp to 45,000 litres, subject to the Rules. Storage above 5,000 litres without a licence can require a prior report under Rule 140.

The applicable licence and facility approvals must be checked for the exact product, container or tank size, total quantity and proposed activity. Storage approval does not by itself authorise filling, decanting, repacking or transfer.

Quick examples for an initial enquiry
ProductPreliminary direction
Toluene, xylene, hexane or heptaneGenerally within the petroleum definition; check the flash point.
Mineral spirits or solvent naphthaGenerally within the petroleum definition; verify the exact grade.
Inflammable thinner containing a liquid hydrocarbonMay meet the petroleum definition; check the finished formulation.
Paint or adhesive containing hydrocarbon solventReview composition and whether the finished mixture is inflammable.
Water-based, nonflammable product without liquid hydrocarbonsGenerally outside the petroleum definition; check other applicable requirements.
Acetone, ethanol or methanolReview the 1952 Act and applicable notifications.
Incomplete SDS or proprietary mixtureRequest further manufacturer information before classification.

What should you send us?

Share the product name and grade, current manufacturer SDS, composition or manufacturer declaration, finished-product flash point and test method, package and container capacity, maximum proposed quantity, and required storage or handling activities. If the SDS says only “proprietary mixture,” we may need further manufacturer clarification.

How Aanant LogistiX reviews a product

Our preliminary review may identify additional product or regulatory information needed. Storage acceptance remains subject to statutory requirements, compatibility, permitted activities and available arrangements.

“Non-PESO” does not mean non-hazardous. Fire safety, MPCB, hazardous-chemical, compatibility and workplace-safety requirements may still apply.

General awareness only. This guide is not a legal classification, licence determination or guarantee of storage acceptance. Verify the current SDS, composition, Acts, Rules, notifications and facility approval conditions for each commercial product.

Official references: Petroleum Act, 1934, Petroleum Rules, 2002 Inflammable Substances Act, 1952 and PESO FAQs.